Surge Protection Inside and Outside the Driver: MOVs, TVS and Coordinated SPDs
Most voltage surges that damage LED drivers never involve a direct lightning strike. They come from lightning striking somewhere nearby, from switching of large loads on the same network, or from faults elsewhere on the grid. These events inject a transient overvoltage onto the AC line, and the duration is short but the energy can be substantial. The lighting industry tests for them using IEC 61000-4-5, which defines a combined wave: a 1.2/50 microsecond voltage waveform and an 8/20 microsecond current waveform. A driver surge rating is its result on that test, and the level tells the specifier how much exposure the product can survive.
Inside the driver, the first line of defense is a metal oxide varistor, or MOV, connected across line and neutral. A varistor is a voltage-dependent resistor: below its clamping voltage it passes almost no current, and above it the resistance collapses, diverting surge energy away from the downstream circuitry. Some designs add a gas discharge tube for higher energy handling or a TVS diode for tighter clamping on sensitive rails. The input fuse sits behind them, ready to open if a surge degrades the protection itself, so that a damaged protector does not leave the driver connected to the mains indefinitely.
The internal protection has a hard limit. A small MOV can absorb only a limited amount of energy, and each significant surge ages it: the clamping voltage drifts and leakage current rises. After repeated events the varistor can fail short, which is why a thermal fuse or disconnect sits alongside it in well-built drivers. Relying on the internal MOV alone is acceptable for ordinary indoor mains, but not for exposed locations where surges arrive often and with more energy, because the internal device is sized for occasional events, not for a steady diet of them.
Where the risk is higher, a coordinated external surge protective device is the correct answer. SPDs for AC low-voltage installations are classified and tested under the IEC 61643 series, with the current structure being IEC 61643-01:2024 for general requirements and IEC 61643-11:2025 for devices connected to AC power systems. The SPD is installed upstream of the driver, sized by its discharge capability and protection level, and it carries the bulk of the surge energy so the internal MOV sees only the remainder. This two-layer arrangement is how installations handle both frequent small events and rare large ones.
Coordination is about voltage, not just energy. The SPD must clamp early enough, and its residual voltage, the let-through, must stay below the withstand level of the driver. Lead length matters: a long conductor between SPD and equipment adds inductance, and the surge current through it produces a voltage drop that appears across the protected device, so a well-chosen SPD can be defeated by poor wiring. Install the SPD as close to the equipment as practical, keep the leads short and straight, and bond it to the same earth reference as the driver.
The practical rule for specifiers is to match protection to exposure. Indoor luminaires on a normal branch rarely need more than the driver internal rating. Outdoor signage, parking structures, and long overhead runs justify a Type 2 SPD at the panel or at the fixture group. And because SPDs wear out, choose units with an end-of-life indicator and check it during maintenance, rather than assuming the protection is still there years after installation, when the components inside may have already degraded.